Conventional fire alarm control panel BP-FD-CCP100 - Blaupunkt
Conventional fire alarm control panel BP-FD-CCP100
- It has 2 level control mode by a lock
- It has 24VDC power supply output
- It has FIRE and FAULT signal output
- It has 2 general sounders output
- Each zone has 1 circuit detectors input
- Each zone can be disabled by a button
- It has RESET button to reset the panel
- It has SILENCE button to stop BUZZER and SOUNDERS
- It has EVACUATE button to start a manual fire alarm immediately
- It has an optional GSM module for fire alarm by SMS
- It is economic, user-friendly and easy maintenance
Ref : 10757
Technical specification
| Model: BP-FD-CCP100 | |
| Power specification | |
| Mains supply voltage | 110VAC or 220VAC |
| Internal power supply | 27.2VDC |
| Total output current limited | 500mA@240VAC |
| Main supply monitor for fault | YES |
| Battery protection for low voltage | YES |
| Batteries (default configuration) | 12V2.3AH*2 |
| Detector circuit specification | |
| Number of circuits | 1 |
| Line fault monitor for open circuit | YES |
| Line fault monitor for short circuit | YES |
| Line fault monitor for detector removal | Yes, if end of line monitor unit fitted in place of end of line resistor |
| End of line device | 6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold) |
| Detector continuity diodes | Silicon 1N4001or Schottky type (required if end of line monitor unit fitted to give detector removal fault) |
| Call point resistor value | 470 to 680Ω, 0.5 or 1 watt |
| Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA). Note: if end of line monitor unit is fitted, for correct operation maximum voltage drop must not exceed 12 volts |
| Maximum number of manual call points per zone | No limit |
| Sounder circuit specification | |
| Number of general circuits | 2 |
| End of line resistor value | 6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold) |
| Line fault monitor for open circuit | Yes |
| Line fault monitor for short circuit | Yes |
| Outputs fused AT | 600mA |
| Maximum number of bells @50mA of each Sounder output | 12 |
| Fuses | |
| Battery fuse | 1.85A resettable fuse |
| Sounder outputs | 400mA F 20mm |
| Fire output | |
| Output type | NC and NO relay |
| Maximum current | 100mA |
| Connection block | |
| Largest acceptable conductor size | 2.5mm2 |
| Smallest acceptable conductor size | 0.75mm2 |
| Size and weight | |
| Dimensions (mm) | 272 x 200 x 70 |
| Weight (with batteries) | 5.5kg |